ATEX

The framework for equipment in potentially explosive atmospheres. The zone defined by the operator in the explosion protection document determines the required equipment category; explosion group and temperature class are added. Pneumatic units are often the simpler route here because no electric drive sits in the field.

Also
Explosion protection · Hazardous area · Directive 2014/34/EU
Also known as
  • Explosion protection
  • Hazardous area
  • Directive 2014/34/EU
01

Two directives, two addressees

The abbreviation ATEX stands for two European directives. Directive 2014/34/EU addresses manufacturers: it sets the requirements for equipment and protective systems intended for potentially explosive atmospheres. Directive 1999/92/EC addresses operators: it requires explosion risks to be assessed, areas to be classified into zones and the result to be recorded in an explosion protection document. Each country has transposed it into national law – in Germany through the Hazardous Substances Ordinance and the Industrial Safety Ordinance, in Great Britain through DSEAR.

The order is thereby fixed: the operator classifies the zone first, then the equipment is selected for it.

02

Zones and equipment categories

The zone describes how often and for how long a hazardous explosive atmosphere occurs. Zones 0, 1 and 2 apply to gases, vapours and mists, zones 20, 21 and 22 to combustible dusts. Each zone is assigned an equipment category; the letter G or D shows whether the equipment is suitable for gas or dust.

Equipment of a higher category may be used in a less critical zone, but not the other way round.

03

Explosion group and temperature class

Zone and category are not enough. The explosion group describes how easily the substance ignites: for gases IIA, IIB and IIC, with IIC – hydrogen and acetylene – the most demanding; for dusts IIIA, IIIB and IIIC. The temperature class limits the maximum surface temperature of the equipment, which must be below the ignition temperature of the substance.

  • T1: maximum 450 °C
  • T2: maximum 300 °C
  • T3: maximum 200 °C
  • T4: maximum 135 °C
  • T5: maximum 100 °C
  • T6: maximum 85 °C
04

Non-electrical equipment is covered too

Explosion protection is not purely an electrical matter. Directive 2014/34/EU applies to any equipment with its own potential ignition source – including mechanical and pneumatic equipment. Hot surfaces on bearings and brakes, mechanically generated sparks and electrostatic discharge are among the ignition sources listed in EN 1127-1; for non-electrical equipment the EN ISO 80079-36 and -37 series is relevant.

For handling devices this means: material pairings at friction points, dissipative rollers, hoses and coatings and continuous equipotential bonding are part of the ignition hazard assessment.

05

Reading a marking

A non-electrical device may, for example, carry the marking “II 2G Ex h IIB T4 Gb”. II stands for the equipment group outside mining, 2G for category 2 in gas atmospheres, Ex h for the type of protection of non-electrical equipment, IIB for the explosion group, T4 for the temperature class and Gb for the equipment protection level. Such a device is suitable for zone 1 and zone 2, provided the substances belong to group IIA or IIB and their ignition temperature is above 135 °C.

What Entracon offers here is on the matching page.

See what we offer
Overview

Zones and the matching equipment categories

Zone Explosive atmosphere is present Equipment category
0 (gas) / 20 (dust) continuously, for long periods or frequently 1G / 1D
1 (gas) / 21 (dust) occasionally in normal operation 2G / 2D or higher
2 (gas) / 22 (dust) not normally, or only briefly 3G / 3D or higher
Frequently asked questions

Frequently asked questions about ATEX

Who defines the hazardous zone?

The operator, as part of the risk assessment and recorded in the explosion protection document. The manufacturer of a device cannot determine the zone; it supplies for the zone, explosion group and temperature class specified.

Does a purely pneumatic handling device need an ATEX assessment?

Yes, if it is used in a potentially explosive atmosphere. Even without electrical components it can have ignition sources – friction, impact, static charge. The manufacturer carries out an ignition hazard assessment and marks the device accordingly.

Can an existing device be moved into a hazardous area later?

Not as it stands. A device without Ex marking has not been assessed for that use. Whether a conversion is possible has to be examined by the manufacturer or a specialist; a new conformity assessment is then required.

What does the temperature class mean in practice?

It states the highest surface temperature the equipment reaches, even under fault conditions. It must be below the ignition temperature of the substances present; equipment rated T4 also covers T1 to T3.