Guides

Control valves: choosing the characteristic, avoiding cavitation and noise

A control valve with the right Kvs value can still control badly, be noisy or start leaking after a few months. The causes almost always lie in two questions that get too little attention during sizing: which characteristic suits the loop – and what happens to the pressure inside the valve?

Author
Dr.-Ing. Philipp Schwittek
Reading time
8 minutes
Updated
04. October 2026
The key points
  • The characteristic on the data sheet applies at constant pressure drop – in the plant it is distorted into the installed characteristic.
  • The lower the valve authority, the greater the distortion; an equal-percentage characteristic compensates for it.
  • Cavitation occurs when the pressure at the narrowest cross-section falls below the vapour pressure and recovers downstream.
  • Flashing is a property of the system, not of the valve: if the outlet pressure is below the vapour pressure, the fluid stays vaporised.
  • Noise is a design result and can be predicted before purchase.
01

Linear and equal percentage

The characteristic describes how the Kv value changes with travel. With a linear characteristic every equal step in travel gives the same increase in Kv. With an equal-percentage characteristic every equal step gives the same percentage increase relative to the Kv value at that point – the curve starts flat and becomes steeper towards the top.

In figures, for a rangeability of 50:1: at half travel the linear valve has reached about 51 per cent of its Kvs value, the equal-percentage valve about 14 per cent. At three-quarters travel it is roughly 76 against 38 per cent. The equal-percentage valve controls small flows with a lot of travel and therefore with fine resolution.

Both curves apply under a condition that is rarely met in a plant: constant pressure drop across the valve. That is why they are called inherent characteristics.

02

What the system does to the characteristic

As the valve opens, flow increases – and with it the pressure loss in the rest of the loop. Less pressure drop remains for the valve. Flow therefore grows more slowly than the inherent characteristic suggests. What actually results is the installed characteristic: flow against travel, in this system.

How far it departs from the inherent one depends on valve authority. At high authority the shape is largely preserved. At low authority a linear characteristic turns into one that releases almost the entire flow in the first few per cent of travel. Under the same conditions an equal-percentage characteristic is distorted towards linear – and so delivers in operation the behaviour wanted from the control loop.

03

Which characteristic where

The aim is a loop whose gain stays as constant as possible over the load range. The valve characteristic should compensate for what system and process distort.

  • Linear: when the valve takes most of the pressure loss and the pressure drop stays roughly constant over the load range.
  • Equal percentage: when the pressure drop falls markedly with increasing flow – the most common case in loops with a pump and long lines.
  • Equal percentage on heat exchangers too: their output rises steeply at low flow and then flattens; the characteristic compensates for that.
  • In case of doubt the calculated installed characteristic for the actual loop decides, not habit.
04

Cavitation: when the liquid boils inside the valve

At the narrowest cross-section of a valve velocity is highest and pressure lowest; downstream the pressure partly recovers. If it falls below the vapour pressure of the liquid at the narrowest point, vapour bubbles form. If it rises above the vapour pressure again downstream, the bubbles collapse abruptly. The resulting pressure pulses strike plug, seat and body wall.

Cavitation is recognised by a crackling noise, as if gravel were being conveyed through the line, by vibration and – on the dismantled valve – by rough, pitted surfaces. With severe cavitation the flow also stops increasing with pressure drop.

How susceptible a valve is depends on its pressure recovery. Designs with a streamlined flow path – ball valves, butterfly valves – recover pressure strongly and cavitate earlier than globe valves. Manufacturers state characteristic values for this: the pressure recovery factor F_L and a value for the pressure ratio at which cavitation begins.

05

Flashing: vaporisation that stays

If the pressure downstream of the valve is permanently below the vapour pressure, the bubbles no longer collapse. Part of the fluid leaves the valve as vapour, and the line downstream carries a mixture of liquid and vapour at high velocity. That is flashing.

The damage pattern is different: smooth surfaces that look washed out rather than pitted craters, caused by droplets striking at high velocity. Above all, flashing is not a matter of valve design. Whether it occurs is decided by outlet pressure and temperature – that is, by the system. A different valve can reduce the consequences, not remove the cause.

06

What helps

Against cavitation, anything helps that prevents the pressure from falling below the vapour pressure in a single step. Against flashing, it helps to place the vaporisation where it does no harm.

  • Reduce pressure in stages: multi-stage trims or drilled plugs divide the pressure drop so that no stage falls below the vapour pressure.
  • Choose a design with low pressure recovery – a globe valve rather than a butterfly valve.
  • Change the location: to where pressure is higher and temperature lower.
  • Raise the back pressure, for example with a restriction downstream of the valve.
  • For flashing: place the valve close to the receiving vessel, enlarge outlet and line, select resistant materials for trim and body.
  • Hardened seat and plug materials extend service life but remove neither cavitation nor noise.
07

Noise: predictable and controllable

With liquids, cavitation is the main source of noise – avoiding it usually gives a quiet valve as well. With gases and steam, noise arises from turbulence and, at high pressure ratios, from shock waves downstream of the restriction. It grows with mass flow and pressure ratio.

The sound level can be predicted before purchase: to IEC 60534-8-3 for gases and vapours, to IEC 60534-8-4 for liquids. The measures fall into two groups. At the source, low-noise trims that split the flow into many small jets and multi-stage pressure reduction are effective. Along the transmission path, heavier pipe walls, acoustic insulation and silencers are effective. Measures at the source also reduce the loading on the valve; measures along the path only reduce what arrives outside.

Overview

Telling cavitation and flashing apart

Aspect Cavitation Flashing
Condition pressure falls below vapour pressure inside the valve and recovers above it downstream outlet pressure stays below vapour pressure
What happens vapour bubbles collapse abruptly fluid leaves the valve as a mixture of liquid and vapour
Noise crackling, like gravel in the line more of a hiss
Damage pattern rough, pitted surfaces smooth, washed-out surfaces
Cause lies in valve design and pressure ratio outlet pressure and temperature of the system
Remedy staged pressure reduction, higher back pressure, different location location, enlarged outlet, resistant materials
Frequently asked questions

Frequently asked questions about Characteristic and cavitation

Does a larger valve help against cavitation?

No. The pressure drop is set by the system, not by the valve. A larger valve takes the same pressure drop at lower travel – with higher velocity at the seat and poorer controllability. What works are trims that reduce pressure in stages, or a different location.

How can I tell in operation whether a valve is cavitating?

By the noise – a crackling that increases with pressure drop – by vibration of the line and by the fact that flow no longer increases although the valve opens further. A calculation with measured inlet pressure, outlet pressure and fluid temperature gives certainty.

Linear or equal percentage – which is the safe choice?

In loops with a pump, long lines or heat exchangers the equal-percentage characteristic is usually the better choice because the pressure drop across the valve falls as flow increases. Linear suits loops where the valve carries almost the entire pressure loss. The decision is made on valve authority, not habit.

Can flashing be avoided with a different valve?

No. If the pressure downstream of the valve is below the vapour pressure, part of the fluid vaporises – whichever valve is installed. What can be influenced are the location, the velocity downstream of the valve and the resistance of the materials.

At what point is a control valve too loud?

The owner defines that in the specification, usually as a sound pressure level at a distance of one metre. For occupational safety, German regulations set action values of 80 and 85 dB(A) for daily exposure. A valve that is persistently very loud is also a sign of high mechanical loading on valve and line.

About the author

Dr.-Ing. Philipp Schwittek

Managing Director, Entracon Planungsgesellschaft mbH

Engineer with a doctorate, specialising in plant engineering, digital design and process automation – from simulation through to commissioning.

  • Sizing
  • Design
  • Plant engineering
  • Standards and safety
Contact

Still a question open?

A short conversation usually settles more than three quotations. You reach an engineer directly, not a queue.

Reach Entracon

How can we help?

Chat is not staffed right now. We are back for you tomorrow from 08:00. Just request a call-back – we'll get back to you.
Send an e-mail info@entracon.de
Or call us directly +49 234 5414010